Permit: T10OT01023

Parcel: 10602011F

Inspection Status: Denied

Inspection History: FIRE - FINAL

Permit Number - T10OT01023

Inspection Description - FIRE - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
05/13/2010 FIRE - FINAL Denied 1. Coverage for extinguisher system on hood needs to be checked out not properly covered.
2. All cooking equipment shall be 6 inches inside hood coverage. Need to move 6 burner stove/grill on east end over.
3. Need to clean hood of all grease from roof top to equipment.
4. Occ. Load set for 65 only one exit need two exits opening outward.
5. Floor plans do not reflect what is on site need better plans showing the proper floor plan.