Inspection Status: Denied
Inspection History: FIRE - FINAL
Permit Number - T10OT01023
Inspection Description - FIRE - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/13/2010 | FIRE - FINAL | Denied | 1. Coverage for extinguisher system on hood needs to be checked out not properly covered. 2. All cooking equipment shall be 6 inches inside hood coverage. Need to move 6 burner stove/grill on east end over. 3. Need to clean hood of all grease from roof top to equipment. 4. Occ. Load set for 65 only one exit need two exits opening outward. 5. Floor plans do not reflect what is on site need better plans showing the proper floor plan. |