Permit: T10OT00760
Permit Details
Apply Date:
04/07/2010
Applicant:
JAY AMIM
Description:
C OF O: MOTEL 6
Permit Reviews
Permit Number - T10OT00760
Permit Status: Expired
Permit Description: C OF O: MOTEL 6
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
04/07/2010 | C OF O | 04/07/2010 | COMPLETED |
Outstanding Inspections
Permit Status: Expired
Permit Number: T10OT00760
Permite Description: C OF O: MOTEL 6
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/08/2010 | CERTIFICATE OF OCCUPANCY | N/A | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY CLIENT 2) NO C OF O FIRE INSPECTION |
04/08/2010 | FIRE - FINAL | N/A | Denied | 1. 2nd Floor south hallway pull station needs testing pulled from wall. 2. 2nd floor north hallway closet cover plates needs on switch and outlet. 3. Exit signs replace battery back and make sure power in on for 120V. Wiring to some of the exits not weather tight need to rewire. 4. Southend pull station repair pulled out of wall. 5. Room 319 replace smoke det. not loud. 6. Need cover plate on 6x6 elect. bax behind washer. |