Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
12/28/2010
Applicant:
HADLOCK STACEY
Description:
COMPLIANCE FOR REPLACE FURNACE & Make code required repairs to 70k BTU gas furnace installed by others.
Contractors:
  • TRON MECHANICAL INC

Outstanding Activity Conditions

Permit Number - T10ME00734
Permit Status: Final
Permit Description: COMPLIANCE FOR REPLACE FURNACE & Make code required repairs to 70k BTU gas furnace installed by others.
Total Outstanding Activity Conditions - 1
Date Name
12/28/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T10ME00734
Permit Description: COMPLIANCE FOR REPLACE FURNACE & Make code required repairs to 70k BTU gas furnace installed by others.
Total Completed Inspections - 3
Date Description Inspector Results Comments
12/30/2010 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :*
1) FLUE PIPE NOT MECHANICALLY ATTACHED TO UNIT
2) PROVIDE APPROVED CORD CONNECTORS WHERE WIRE PASSES THRU CABINET
3) PROVIDE TIGHT JOINTS ON ALL FLUE PIEP FITTINGS MINIMUM 1" INSERTION
4) ALL PVC JOINTS ARE TO BE PRIMED, PRIMER IS TO BE PURPLE IN COLOR
5) SECONDARY DRAIN TO DUMP IN A MONITORED LOCATION
6) ALL PVC EXPOSED TO EXTERIOR IS TO BE COATED
7) ALL LINE SET INSULATION EXPOSED TO EXTERIOR IS TO BE COATED
8) STRAP GAS PIPING AT UNIT
9) FLUE PIPE ON EXTERIOR OF BLDG NOT COMPLETE
01/04/2011 MECHANICAL - INTERMEDIATE MRAMBER Approved
01/18/2011 PERMIT FINALED JWEATHER Approved