Permit Details

Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
5440 S CANADA DR
Address NEW:
5440 S CANADA DR
Apply Date:
10/06/2010
Applicant:
ARIZONA S FINEST HEATING AND COOLING L L C
Description:
INSTALL:5 TON HEAT PUMP (T10CM02393 T10EL02193)
Contractors:
  • ARIZONA S FINEST HEATING AND COOLING L L C

Permit Reviews

Permit Number - T10ME00613
Permit Status: Final
Permit Description: INSTALL:5 TON HEAT PUMP (T10CM02393 T10EL02193)
Start Date Submittal Complete Date Status  
10/06/2010 MECHANICAL 10/13/2010 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T10ME00613
Permit Status: Final
Permit Description: INSTALL:5 TON HEAT PUMP (T10CM02393 T10EL02193)
Total Outstanding Activity Conditions - 1
Date Name
10/06/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T10ME00613
Permit Description: INSTALL:5 TON HEAT PUMP (T10CM02393 T10EL02193)
Total Completed Inspections - 3
Date Description Inspector Results Comments
12/17/2010 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE MINIMUM R-8 DUCT LINER (2") ON ALL DUCT EXPOSED TO EXTERIOR
2) ALL PVC JOINTS ARE TO BE PRIMERED AND ALL PRIMER IS TO BE PURPLE IN COLOR PER UPC
3) ALL PVC EXPOSED TO DAYLIGHT IS TO BE COATED TO PROVIDE UV PROTECTION
4) ALL CONDUIT IS TO BE BLOCKED UP OFF ROOF
5) UNIT DATA PLATE NOT INDENTIFIED
6) CONDENSATE PIPING NOT TO TERMINATE AT SIDE WALK OR ANY OTHER HARD SURFACE LOCATION
7) PVC PIPE STRAPPING AND OR BLOCKING NOT TO EXCEED 4' HORIZONTAL AND 10' VERTICAL
01/04/2011 MECHANICAL - INTERMEDIATE MRAMBER Approved
01/18/2011 PERMIT FINALED JWEATHER Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CONSTRPLANS VIEW