Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/17/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE MINIMUM R-8 DUCT LINER (2") ON ALL DUCT EXPOSED TO EXTERIOR 2) ALL PVC JOINTS ARE TO BE PRIMERED AND ALL PRIMER IS TO BE PURPLE IN COLOR PER UPC 3) ALL PVC EXPOSED TO DAYLIGHT IS TO BE COATED TO PROVIDE UV PROTECTION 4) ALL CONDUIT IS TO BE BLOCKED UP OFF ROOF 5) UNIT DATA PLATE NOT INDENTIFIED 6) CONDENSATE PIPING NOT TO TERMINATE AT SIDE WALK OR ANY OTHER HARD SURFACE LOCATION 7) PVC PIPE STRAPPING AND OR BLOCKING NOT TO EXCEED 4' HORIZONTAL AND 10' VERTICAL |