Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T10ME00613

Parcel: 137101880


Addresses:

5440 S CANADA DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/04/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/17/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE MINIMUM R-8 DUCT LINER (2") ON ALL DUCT EXPOSED TO EXTERIOR
2) ALL PVC JOINTS ARE TO BE PRIMERED AND ALL PRIMER IS TO BE PURPLE IN COLOR PER UPC
3) ALL PVC EXPOSED TO DAYLIGHT IS TO BE COATED TO PROVIDE UV PROTECTION
4) ALL CONDUIT IS TO BE BLOCKED UP OFF ROOF
5) UNIT DATA PLATE NOT INDENTIFIED
6) CONDENSATE PIPING NOT TO TERMINATE AT SIDE WALK OR ANY OTHER HARD SURFACE LOCATION
7) PVC PIPE STRAPPING AND OR BLOCKING NOT TO EXCEED 4' HORIZONTAL AND 10' VERTICAL