Completed Inspections

Permit Status: Final
Permit Number: T10ME00562
Permit Description: INSTALLATION OF CONDENSOR. (REPLACEMENT)
Total Completed Inspections - 2
Date Description Inspector Results Comments
11/19/2010 MECHANICAL - INTERMEDIATE MRAMBER Approved IVRS - Inspection :*
12/17/2010 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL PVC JOINTS ARE TO HAVE PRIMERED JOINTS, ALL PRIMER IS TO BE PURPLE IN COLOR
2) PROVIDE SECONDARY DRAIN AT EVAP COIL
3) LINE SET INSULATION NOT PROPERLY INSTALLED
4) PROVIDE PROPER CLAMP BUSHINGS WHEN PASSING INTO CABINET WITH LOW VOLTAGE WIRING
5) LINE SET INSULATION IS TO BE COATED AT EXTERIOR
6) PVC EXPOSED TO EXTERIOR IS TO BE COATED
7) REMOVE WHITE WIRE FROM LINE VOLTAGE TO CONDENSOR
8) OUTDOOR STAT WIRE TO BE IN CONDUIT
9) CONDENSATE OVER FUSED