Permit: T10ME00562

Parcel: 129060240


Addresses:

2907 E 20TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/10/2013 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/12/2013 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
04/12/2013 MECHANICAL - FINAL Partial Approval MET WITH CONTRACTOR TO DISCUSS ISSUES. CONTRACTOR INFORMED ANY FURTHER FAILED INSPECTIONS WILL BE RE-FEE ASSESSED.
03/29/2013 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SINGLE WALL FLUE TO HAVE MINIMUM 6" CLEARENCE TO COMBUSTIBLES ( PVC PIPE)
2) TRAP STILL NOT VENTED SECONDARY NOT PROPERLY INSTALLED.
3) LINE SET NOT COATED
4) CLAMP ON LOW VOLTAGE STILL NOT INSTALLED
5) OUTSIDE STAT WIRE STILL NOT IN CONDUIT.
04/01/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
1) CONDENSATE DRAIN NOT PROPERLY INSTALLED, P-TRAP NEEDS VENT
2) PREVIOUS INSPECTION NOT COMPLETE A REFEE IS BEING ASSESED TO THIS PERMIT
3) CONTRACTOR TO BE ON SITE FOR NEXT INSPECTION
12/17/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL PVC JOINTS ARE TO HAVE PRIMERED JOINTS, ALL PRIMER IS TO BE PURPLE IN COLOR
2) PROVIDE SECONDARY DRAIN AT EVAP COIL
3) LINE SET INSULATION NOT PROPERLY INSTALLED
4) PROVIDE PROPER CLAMP BUSHINGS WHEN PASSING INTO CABINET WITH LOW VOLTAGE WIRING
5) LINE SET INSULATION IS TO BE COATED AT EXTERIOR
6) PVC EXPOSED TO EXTERIOR IS TO BE COATED
7) REMOVE WHITE WIRE FROM LINE VOLTAGE TO CONDENSOR
8) OUTDOOR STAT WIRE TO BE IN CONDUIT
9) CONDENSATE OVER FUSED
11/19/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PHONED AT 8:40 AM AT 9:30 STILL DID NOT RECEIVE A CALL BACK FROM MESSAGE LEFT
2) ANY FURTHER FAILED INSPECTIONS WILL RESULT IN A RE-FEE
09/20/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLEASE SCHEDULE AN INSPECTION WHEN SOMEONE WILL BE HERE IN THE A.M.
09/07/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*