Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Apply Date:
07/27/2010
Applicant:
WALTER VIRGINIA
Description:
replace split system heat pump, 15 seer, 5 ton. Like for like.
Contractors:
  • RITEWAY VENTILATING *C*

Outstanding Activity Conditions

Permit Number - T10ME00466
Permit Status: Expired
Permit Description: replace split system heat pump, 15 seer, 5 ton. Like for like.
Total Outstanding Activity Conditions - 1
Date Name
07/27/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10ME00466
Permite Description: replace split system heat pump, 15 seer, 5 ton. Like for like.
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
08/02/2010 MECHANICAL - FINAL N/A Partial Approval IVRS - Inspection :*
1) PROVIDE A BUSHING IN FAN COIL KNOCKOUT AT LINE SET CONNECTION
2) 30 AMP BREAKER IN FAN COIL NOT ADEQUATE FOR THE HEAT STRIP IDENTIFIED ON DATA PLATE
3) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX

Completed Inspections

Permit Status: Expired
Permit Number: T10ME00466
Permit Description: replace split system heat pump, 15 seer, 5 ton. Like for like.
Total Completed Inspections - 1
Date Description Inspector Results Comments
08/02/2010 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*

Documents

File Name Document Type  
None DOCUMENTS VIEW