Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE A BUSHING IN FAN COIL KNOCKOUT AT LINE SET CONNECTION 2) 30 AMP BREAKER IN FAN COIL NOT ADEQUATE FOR THE HEAT STRIP IDENTIFIED ON DATA PLATE 3) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX |