Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
3408 E SILVERLAKE RD
Apply Date:
06/18/2010
Applicant:
MOSSBERG JONATHAN
Description:
remove and replace heat pump on roof
Contractors:
  • MOSSBERG CONSTRUCTION L L C

Permit Reviews

Permit Number - T10ME00374
Permit Status: Expired
Permit Description: remove and replace heat pump on roof
Start Date Submittal Complete Date Status  
11/18/2010 MECHANICAL 11/18/2010 ACTIVE Review Details

Outstanding Activity Conditions

Permit Number - T10ME00374
Permit Status: Expired
Permit Description: remove and replace heat pump on roof
Total Outstanding Activity Conditions - 1
Date Name
06/18/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10ME00374
Permite Description: remove and replace heat pump on roof
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
07/15/2010 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THIS IS A NEW INSTALLATION NOT A REPLACEMENT OR CHANGE OUT, REVISE PERMIT WITH CITY OF TUCSON PRIOR TO NEXT INSPECTION
2) ALL PVC PIPE JOINTS AND FITTINGS ARE TO BE PRIMED, PRIMER IS TO BE PURPLE IN COLOR
3) PROVIDE APPROVED ROOF LOAD CALC FROM FROM CITY OF TUCSON
4) PROVIDE APPROVED STAND SPANNING TRUSSES AS CALLED OUT ON ROOF LOAD CALC FORM
5) ALL DUCT EXTERIOR OR IN VENTED ATTI OR OUTSIDE THERMAL ENVELOP OF BLDG IS TO HAVE A MIN. R-8 INSULATION (2" LINER)
6) UNIT DATA PLATE NOT IDENTIFIED (DO YOU HAVE HEAT STRIPS)
7) PROVIDE ROOF JACK AT SERVICE OUTLET

Documents

File Name Document Type  
None DOCUMENTS VIEW