Permit: T10ME00374

Parcel: 130111480

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/15/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THIS IS A NEW INSTALLATION NOT A REPLACEMENT OR CHANGE OUT, REVISE PERMIT WITH CITY OF TUCSON PRIOR TO NEXT INSPECTION
2) ALL PVC PIPE JOINTS AND FITTINGS ARE TO BE PRIMED, PRIMER IS TO BE PURPLE IN COLOR
3) PROVIDE APPROVED ROOF LOAD CALC FROM FROM CITY OF TUCSON
4) PROVIDE APPROVED STAND SPANNING TRUSSES AS CALLED OUT ON ROOF LOAD CALC FORM
5) ALL DUCT EXTERIOR OR IN VENTED ATTI OR OUTSIDE THERMAL ENVELOP OF BLDG IS TO HAVE A MIN. R-8 INSULATION (2" LINER)
6) UNIT DATA PLATE NOT IDENTIFIED (DO YOU HAVE HEAT STRIPS)
7) PROVIDE ROOF JACK AT SERVICE OUTLET
07/07/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) CALLED NUMBER SHOWN, NO ANSWER AND VOICE BOX FULL, UNABLE TO LEAVE MESSAGE
07/02/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) SECURE ANGLE IRON STAND TO THE STRUCTURE AND RECALL FOR FINAL