Permit: T10ME00290
Permit Details
Apply Date:
05/17/2010
Applicant:
WALTER VIRGINIA
Description:
Replace (2) 5 ton gas package units. Like for like. Roof mounted.
Contractors:
- RITEWAY VENTILATING *C*
Outstanding Activity Conditions
Permit Number - T10ME00290
Permit Status: Expired
Permit Description: Replace (2) 5 ton gas package units.
Like for like. Roof mounted.
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/17/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T10ME00290
Permite Description: Replace (2) 5 ton gas package units.
Like for like. Roof mounted.
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2010 | MECHANICAL - INTERMEDIATE | N/A | Partial Approval | IVRS - Inspection :* |
| 06/01/2010 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VERIFY 2" LINER IN NEW DUCT ON ROOF 2) PROVIDE FILTERED O.S.A. ON UNITS 3) CONDENSATE MUST TERMINATE AT AN APPROVED LOCATION 4) WHEN TIE IN TO CONDENSATE LINES TOGETHER THE MIN. PIPE SIZE IS 1" 5) BLOCKING FOR P.V.C. PIPING NOT TO EXCEED 48" 6) PROVIDE GAS PRESSURE TEST OR LEAK DETECTING BUBBLES FOR NEW GAS PIPING ON ROOF |