Permit: T10ME00290

Parcel: 13017146F


Addresses:

1635 S ALVERNON WY

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/01/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) VERIFY 2" LINER IN NEW DUCT ON ROOF
2) PROVIDE FILTERED O.S.A. ON UNITS
3) CONDENSATE MUST TERMINATE AT AN APPROVED LOCATION
4) WHEN TIE IN TO CONDENSATE LINES TOGETHER THE MIN. PIPE SIZE IS 1"
5) BLOCKING FOR P.V.C. PIPING NOT TO EXCEED 48"
6) PROVIDE GAS PRESSURE TEST OR LEAK DETECTING BUBBLES FOR NEW GAS PIPING ON ROOF