Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
1859 S SUNBURST DR
Apply Date:
05/03/2010
Applicant:
S G H AND C L L C
Description:
MECHANICAL:REPLACE 3 1/2 TON A/C UNIT
Contractors:
  • S G H AND C L L C

Outstanding Activity Conditions

Permit Number - T10ME00253
Permit Status: Expired
Permit Description: MECHANICAL:REPLACE 3 1/2 TON A/C UNIT
Total Outstanding Activity Conditions - 1
Date Name
05/03/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10ME00253
Permite Description: MECHANICAL:REPLACE 3 1/2 TON A/C UNIT
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
07/08/2010 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDENSATE PUMP NOT NECESSARY
2) REMOVE PUMP AND TERMINATE INTO THE DRAIN PROVIDED
3) SEAL PLATFROM AROUND DRAIN LINE
4) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
5) MARK FAN COIL WITH HEAT STRIP INFO AND PROVIDE PROPER OVERCURRENT PROTECTION
6) PROPERLY ID CIRCUIT BREAKER
7) PROVIDE BUSHING IN FAN COIL AT DISCHARGE LINE
8) INSULATE METAL SLEEVE ON FAN COIL
9) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX
10) SECURE THE DISCONNECT ON ROOF
11) SLEEPERS ON ROOF NEED TO SPAN THE ROOF JOISTS
12) EXPOSE THE BURIED CONDUIT, PLASTIC MUST BE MINIMUM 18" DEEP AND PROVIDE A TRACER WIRE