Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/25/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 07/08/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE PUMP NOT NECESSARY 2) REMOVE PUMP AND TERMINATE INTO THE DRAIN PROVIDED 3) SEAL PLATFROM AROUND DRAIN LINE 4) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE 5) MARK FAN COIL WITH HEAT STRIP INFO AND PROVIDE PROPER OVERCURRENT PROTECTION 6) PROPERLY ID CIRCUIT BREAKER 7) PROVIDE BUSHING IN FAN COIL AT DISCHARGE LINE 8) INSULATE METAL SLEEVE ON FAN COIL 9) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX 10) SECURE THE DISCONNECT ON ROOF 11) SLEEPERS ON ROOF NEED TO SPAN THE ROOF JOISTS 12) EXPOSE THE BURIED CONDUIT, PLASTIC MUST BE MINIMUM 18" DEEP AND PROVIDE A TRACER WIRE |