Permit: T10ME00253

Parcel: 136084510


Addresses:

1859 S SUNBURST DR

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/25/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
07/08/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDENSATE PUMP NOT NECESSARY
2) REMOVE PUMP AND TERMINATE INTO THE DRAIN PROVIDED
3) SEAL PLATFROM AROUND DRAIN LINE
4) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
5) MARK FAN COIL WITH HEAT STRIP INFO AND PROVIDE PROPER OVERCURRENT PROTECTION
6) PROPERLY ID CIRCUIT BREAKER
7) PROVIDE BUSHING IN FAN COIL AT DISCHARGE LINE
8) INSULATE METAL SLEEVE ON FAN COIL
9) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX
10) SECURE THE DISCONNECT ON ROOF
11) SLEEPERS ON ROOF NEED TO SPAN THE ROOF JOISTS
12) EXPOSE THE BURIED CONDUIT, PLASTIC MUST BE MINIMUM 18" DEEP AND PROVIDE A TRACER WIRE