Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Apply Date:
04/26/2010
Applicant:
D AND H AIR CONDITIONING CO,*C
Description:
REPLACE; 5 TON GAS SPLIT SYSTEM, GROUND MOUNT (APA)
Contractors:
  • D AND H AIR CONDITIONING CO,*C

Outstanding Activity Conditions

Permit Number - T10ME00232
Permit Status: Expired
Permit Description: REPLACE; 5 TON GAS SPLIT SYSTEM, GROUND MOUNT (APA)
Total Outstanding Activity Conditions - 1
Date Name
04/26/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10ME00232
Permite Description: REPLACE; 5 TON GAS SPLIT SYSTEM, GROUND MOUNT (APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
05/03/2010 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 3/8" ID GAS FLEX NOT ADEQUATE FOR 110,00 BTU 1/2" GAS PIPE IS NOT ADEQUATE FOR 110,000 BTU FURNACE 100' FROM THE METER. 1" MAY BE REQUIRED
2) GFI SERVICE RECEPT NOT WIRED CORRECTLY. CANNOT USE THE A/C CIRCUIT, NO NEUTRAL WIRE
3) EXTEND TO THE FURNACE VENT MIN 3' ABOVE COMBUSTION AIR INTAKE