Permit: T10ME00232

Parcel: 11460008K

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/03/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 3/8" ID GAS FLEX NOT ADEQUATE FOR 110,00 BTU 1/2" GAS PIPE IS NOT ADEQUATE FOR 110,000 BTU FURNACE 100' FROM THE METER. 1" MAY BE REQUIRED
2) GFI SERVICE RECEPT NOT WIRED CORRECTLY. CANNOT USE THE A/C CIRCUIT, NO NEUTRAL WIRE
3) EXTEND TO THE FURNACE VENT MIN 3' ABOVE COMBUSTION AIR INTAKE
04/29/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) I'M SORRY I WAS UNABLE TO MAKE IT HERE BEFORE 11:00 AM, PLEASE RESCHEDULE WHEN YOU KNOW YOU WILL BE HOME
2) PLEASE HAVE YOUR CONTRACTOR LEAVE YOUR PHONE NUMBER ON THE MESSAGE AND I WILL CALL YOU WITH AN ETA
04/27/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLEASE SCHEDULE YOUR INSPECTION WHEN SOMEONE WILL BE HOME