Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/03/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 3/8" ID GAS FLEX NOT ADEQUATE FOR 110,00 BTU 1/2" GAS PIPE IS NOT ADEQUATE FOR 110,000 BTU FURNACE 100' FROM THE METER. 1" MAY BE REQUIRED 2) GFI SERVICE RECEPT NOT WIRED CORRECTLY. CANNOT USE THE A/C CIRCUIT, NO NEUTRAL WIRE 3) EXTEND TO THE FURNACE VENT MIN 3' ABOVE COMBUSTION AIR INTAKE |
|
| 04/29/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) I'M SORRY I WAS UNABLE TO MAKE IT HERE BEFORE 11:00 AM, PLEASE RESCHEDULE WHEN YOU KNOW YOU WILL BE HOME 2) PLEASE HAVE YOUR CONTRACTOR LEAVE YOUR PHONE NUMBER ON THE MESSAGE AND I WILL CALL YOU WITH AN ETA |
|
| 04/27/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE SCHEDULE YOUR INSPECTION WHEN SOMEONE WILL BE HOME |