Permit: T10EL01032
Permit Details
Apply Date:
05/04/2010
Applicant:
MARIA E LIRA
Description:
ELEC RECONNECT
Outstanding Activity Conditions
Permit Number - T10EL01032
Permit Status: Expired
Permit Description: ELEC RECONNECT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/04/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T10EL01032
Permite Description: ELEC RECONNECT
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2010 | ELECTRIC - RECONNECT | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
| 05/10/2010 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KITCHEN RECEPTS TO BE GFCI PROTECTED 2) GROUNDED RECEPT ON NON GROUNDED CIRCUITS 3) SUB PANEL IN CLOSET NOT INSTALLED TO CODE 4) COOLER SWITCH NOT INSTALLED TO BOX 5) SMOKE DETECTORS NEEDED IN HALL AND BEDROOMS-INSTALL PER INSTRUCTIONS 6) ONLY ONE NEUTRAL CONDUCTOR TO A TERMNATION 7) FILL UNUSED OPENING PANEL COVER 8) DRYER WIRING TO BE FOR WET LOCATION 9) MISSING GAS AND WATER BONDS 10) BOX AT REAR LIGHT NOT PROPERLY WIRED |