Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KITCHEN RECEPTS TO BE GFCI PROTECTED 2) GROUNDED RECEPT ON NON GROUNDED CIRCUITS 3) SUB PANEL IN CLOSET NOT INSTALLED TO CODE 4) COOLER SWITCH NOT INSTALLED TO BOX 5) SMOKE DETECTORS NEEDED IN HALL AND BEDROOMS-INSTALL PER INSTRUCTIONS 6) ONLY ONE NEUTRAL CONDUCTOR TO A TERMNATION 7) FILL UNUSED OPENING PANEL COVER 8) DRYER WIRING TO BE FOR WET LOCATION 9) MISSING GAS AND WATER BONDS 10) BOX AT REAR LIGHT NOT PROPERLY WIRED |
|
| 05/05/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* |