Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T10EL00343
Permit Details
Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
1912 E WATER ST #02
Address NEW:
1912 E WATER ST #02
Apply Date:
02/17/2010
Applicant:
ANNETTE OR ROGER EMERY
Description:
REPAIR: ELECTRICAL SERVICE ENTRANCE T09DV06801
Permit Reviews
Permit Number - T10EL00343
Permit Status: Final
Permit Description: REPAIR: ELECTRICAL SERVICE ENTRANCE T09DV06801
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 02/17/2010 | ELECTRICAL | 02/17/2010 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T10EL00343
Permit Status: Final
Permit Description: REPAIR: ELECTRICAL SERVICE ENTRANCE T09DV06801
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 02/17/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T10EL00343
Permit Description: REPAIR: ELECTRICAL SERVICE ENTRANCE T09DV06801
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2010 | ELECTRIC - SERVICE UPGRADE | DSANTACR | Approved | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CANNOT DBL LUG IN SERVICE DISC. SW. 2) ISOLATE GROUNDS AND NEUTRALS IN SUB PANEL 3) SUPPORT PVC CONDUITS |
| 10/03/2011 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection :* |