Description:
MECHANICAL:CHILLER, COOLING TOWER, BOILER SOUTH MECHANICAL ROOM
Contractors:
  • ORACLE CONTROL SYSTEMS INC *C*

Permit Reviews

Permit Number - T10CM03483
Permit Status: Expired
Permit Description: MECHANICAL:CHILLER, COOLING TOWER, BOILER SOUTH MECHANICAL ROOM
Start Date Submittal Complete Date Status  
02/17/2011 RESUBMITTAL 03/01/2011 COMPLETED Review Details
03/01/2011 RESUBMITTAL 03/02/2011 COMPLETED Review Details
12/16/2010 OTHER 02/16/2011 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T10CM03483
Permit Status: Expired
Permit Description: MECHANICAL:CHILLER, COOLING TOWER, BOILER SOUTH MECHANICAL ROOM
Total Outstanding Activity Conditions - 1
Date Name
12/16/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10CM03483
Permite Description: MECHANICAL:CHILLER, COOLING TOWER, BOILER SOUTH MECHANICAL ROOM
Total Outstanding Inspections - 8
Last Inspection Date Description Inspector Results Comments
PLUMBING - YARD WTR LINE/TEST N/A Not Inspected
PLUMBING - GAS PRESS TEST FNL N/A Not Inspected
PLUMBING - PROGRESS N/A Not Inspected
05/06/2011 PLUMBING - GAS PRESSURE TEST N/A Partial Approval IVRS - Inspection :*
1) 60 PSI TEST ON WELDED GAS PIPE TO BOILERS IN SOUTH CENTRAL PLAN IS OK
05/09/2011 MECHANICAL - UNDERGROUND N/A Partial Approval IVRS - Inspection :*
1) CHILLED SUPPLY & RETURN, DOMESTIC HOT WATER
2) SUPPLY 100 PSI HYDRO TEST OK TO INSULATE EAST SIDE AND PIPES ACROSS PARKING LOT
3) STILL NEED TEST ON DOMESTIC HOT WATER RETURN
10/14/2011 MECHANICAL - HYDRONIC PIPING N/A Partial Approval IVRS - Inspection :*
1) ROOF TOP PIPING ON BLDGS A, B & C OK
2) PROVIDE INSTALL INSTRUCTIONS FOR FAN COILS AND NEED TO SEE FAN COILS
10/28/2011 MECHANICAL - INTERMEDIATE N/A Partial Approval IVRS - Inspection :*
1) CHECKED BOILERS AND VENTING
12/16/2011 MECHANICAL - FINAL N/A Partial Approval IVRS - Inspection :*
1) NEED TO SEE ALL FAN COILS OLD AND NEW
2) ADD ALL NEW FAN COILS TO PLANS AND PERMIT
3) EVERYTHING ELSE OK

Completed Inspections

Permit Status: Expired
Permit Number: T10CM03483
Permit Description: MECHANICAL:CHILLER, COOLING TOWER, BOILER SOUTH MECHANICAL ROOM
Total Completed Inspections - 3
Date Description Inspector Results Comments
12/16/2011 PLUMBING - FINAL JMILITEL Approved IVRS - Inspection :*
12/16/2011 ELECTRIC - FINAL JMILITEL Approved IVRS - Inspection :*
12/16/2011 ELECTRIC - UNDERGROUND JMILITEL Approved