Permit: T10CM03483

Parcel: 11446027E

Inspection Status: Partial Approval

Inspection History: MECHANICAL - HYDRONIC PIPING

Permit Number - T10CM03483

Inspection Description - MECHANICAL - HYDRONIC PIPING

Inspection Status - Partial Approval

Date Description Inspector Results Comments
10/14/2011 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) ROOF TOP PIPING ON BLDGS A, B & C OK
2) PROVIDE INSTALL INSTRUCTIONS FOR FAN COILS AND NEED TO SEE FAN COILS
09/23/2011 MECHANICAL - HYDRONIC PIPING Partial Approval CHECKED ROOF TOP PIPING 100 PSI HYDROTEST BLDGS D, E, F, G, H, I.
OK TO FINISH INSULATING & CONNECTING BRANCH LINES.
NEED TO SEE FAN COILS.
PROVIDE OVERFLOW SENSORS.
08/26/2011 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) CHECKED HYDRONIC PIPING IN FRONT OF BLDG G, H & E-OK TO INSULATE AND BACKFILL
08/16/2011 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) CHILLED WATER AND DOEMSTIC HOT FROM MIDDLE OF A & B TO END OF C. OK TO INSULATE AND BACKFILL
08/02/2011 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) 100 PSI TEST PIPING FROM FRONT OF OFFICE TO MIDDLE OF BLDG A & B- OK TO INSULATE AND BACKFILL
07/27/2011 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) 100 PSI TEST ON DOMESTIC HOT WATER AND CHILLER PIPING EAST SIDE OF PARKING LOT TO END OF BLDG L. OK TO INSULATE AND BACKFILL
07/07/2011 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) 100 PSI TEST ON REMAINDER OF PARKING LOT PARKING
2) OK TO BACKFILL
06/10/2011 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) 100 PSI HYDOR TEST ON CHILLED WATER AND DOMESTIC HOT WATER FROM MIDWAY OF OFFICES TO FRONT OF BLDG B
2) ALL READY PARTIALED FRAMED
3) OK TO INSULATE AND BACK FILL
06/06/2011 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
100 PSI TEST ON CHILLER + DOMESTIC HOT WATER PIPING FROM SO. CENTRAL PLANT TO MIDWAY TO OFFICES. OK TO INSULATE + BACK FILL.
05/26/2011 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) CHILLER PIPING AND HOT WATER PIPING TO BLDGS D & E OK TO INSULATE
2) 100 PSI TEST OK
05/16/2011 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*.
1) 100 PSI HYDRO TEST CHILLER SUPPLY AND RETURN DOMESTIC HOT SUPPLY & RETURN FROM END OF BLDG
2) I TO MIDDLE OF BLDG 3-OK TO BACKFILL AND INSULATE
04/22/2011 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
04/21/2011 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
1) CHILLER PIPING AND DOMESTIC HOT WATER PIPING IN TRENCH FROM SOUTH CENTRAL PLANT TO BLDG I AND 20' TO NORTH OF SOUTH CENTRAL PLANT
2) 100 PSI HYDRO TEST OK