Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Apply Date:
12/15/2010
Applicant:
N/A
Description:
Temporary CONSTRUCTION TRAILER
Contractors:
  • WITHERS CONSTRUCTION L C , D L

Permit Reviews

Permit Number - T10CM03470
Permit Status: Expired
Permit Description: Temporary CONSTRUCTION TRAILER
Start Date Submittal Complete Date Status  
12/15/2010 MODULAR BUILDINGS 12/21/2010 COMPLETED Review Details
12/21/2010 REVISION - - 1ST 12/21/2010 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T10CM03470
Permit Status: Expired
Permit Description: Temporary CONSTRUCTION TRAILER
Total Outstanding Activity Conditions - 1
Date Name
12/15/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10CM03470
Permite Description: Temporary CONSTRUCTION TRAILER
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
02/25/2011 ELECTRIC - TEMPORARY POLE N/A Partial Approval IVRS - Inspection :*
02/25/2011 ELECTRIC - TEMPORARY SERVICE N/A Partial Approval IVRS - Inspection :*
03/15/2011 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SCHEDULE 80 ABOVE GRADE PANEL AND TRAILER
2) SUPPORT PVC CONDUITS PANEL AND TRAILER
3) PROTECT CONDUCTORS AT PVC FITTINGS 352.46 AND 300.4 PANEL AND TRAILER
4) SECURE FLEX AT TEMP PANEL
5) LABEL BREAKER
6) NEED MAIN BREAKER AT TRAILER TEMP PANEL 225.31 AND 32
7) NEED GROUNDING ELECTRODE SYSTEM AT TRAILER
8) FILL UNUSED OPENINGS PANEL AT TRAILER

Completed Inspections

Permit Status: Expired
Permit Number: T10CM03470
Permit Description: Temporary CONSTRUCTION TRAILER
Total Completed Inspections - 3
Date Description Inspector Results Comments
02/25/2011 ELECTRIC - UFER DSANTACR Approved IVRS - Inspection :*
02/26/2011 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection :*
02/28/2011 TEP CLEARANCE - AM JWEATHER Approved TMPC CLEARED FOR "CONSTRUCTION TRAILER" PER D. SANTACRUZ

Documents

File Name Document Type  
None DOCUMENTS VIEW
001_PLAN.TIF CONSTRPLANS VIEW
None CONSTRPLANS VIEW