Permit: T10CM03470

Parcel: 10304001F

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/15/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SCHEDULE 80 ABOVE GRADE PANEL AND TRAILER
2) SUPPORT PVC CONDUITS PANEL AND TRAILER
3) PROTECT CONDUCTORS AT PVC FITTINGS 352.46 AND 300.4 PANEL AND TRAILER
4) SECURE FLEX AT TEMP PANEL
5) LABEL BREAKER
6) NEED MAIN BREAKER AT TRAILER TEMP PANEL 225.31 AND 32
7) NEED GROUNDING ELECTRODE SYSTEM AT TRAILER
8) FILL UNUSED OPENINGS PANEL AT TRAILER