Permit: T10CM03428
Permit Details
Apply Date:
12/09/2010
Applicant:
N/A
Description:
REPLACE; 3 TON ROOF TOP GAS PACK & WATER HEATER (APA)
Contractors:
- MASCO HOME SERVICES INC *APA*
Outstanding Activity Conditions
Permit Number - T10CM03428
Permit Status: Final
Permit Description: REPLACE; 3 TON ROOF TOP GAS PACK & WATER HEATER (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/09/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T10CM03428
Permit Description: REPLACE; 3 TON ROOF TOP GAS PACK & WATER HEATER (APA)
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2010 | MECHANICAL - FINAL | MRAMBER | Approved | IVRS - Inspection :* 1) PROVIDE R-8 (2") DUCT LINER ON ALL EXTERIOR DUCT 2) DUCT JOINTS NOT SEALED 3) GAS PIPING NOT PROPERLY SUPPORTED 4) ALL PVC JOINTS ARE TO BE PRIMED, PRIMER IS TO BE PURPLE IN COLOR PER UPC 5) COND. PIPE TO BE BLOCKED UP OFF ROOF MINIMUM 1.5" 6) PVC PIPE EXPOSED TO DAYLIGHT IS TO BE UV COATED 7) REMOVE THREADS FROM DISCHARGE END OF COND. PIPE 8) ELECTRIC CONDUIT TO BE BLOCKED UP OFF ROOF MINIMUM 1.5" 9) ITEMS DATED 12/13/10 HAVE BEEM CORRECTED |
| 12/17/2010 | MECHANICAL - INTERMEDIATE | MRAMBER | Approved | IVRS - Inspection :* |
| 12/17/2010 | PLUMBING - FINAL | MRAMBER | Approved | IVRS - Inspection :* |