Permit: T10CM03428

Parcel: 130111790


Addresses:

2327 S HOLLY SV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/06/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/17/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE R-8 (2") DUCT LINER ON ALL EXTERIOR DUCT
2) DUCT JOINTS NOT SEALED
3) GAS PIPING NOT PROPERLY SUPPORTED
4) ALL PVC JOINTS ARE TO BE PRIMED, PRIMER IS TO BE PURPLE IN COLOR PER UPC
5) COND. PIPE TO BE BLOCKED UP OFF ROOF MINIMUM 1.5"
6) PVC PIPE EXPOSED TO DAYLIGHT IS TO BE UV COATED
7) REMOVE THREADS FROM DISCHARGE END OF COND. PIPE
8) ELECTRIC CONDUIT TO BE BLOCKED UP OFF ROOF MINIMUM 1.5"
9) ITEMS DATED 12/13/10 HAVE BEEM CORRECTED
12/13/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE LADDER FOR ROOF ACCESS
2) PROVIDE SEDIMENT TRAP AT W/H GAS PIPING
3) W/H FLUE PIPING NOT INSTALLED PROPERLY (FITTING NOT TIGHT, SHOWING CRIMP)