Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/17/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE R-8 (2") DUCT LINER ON ALL EXTERIOR DUCT 2) DUCT JOINTS NOT SEALED 3) GAS PIPING NOT PROPERLY SUPPORTED 4) ALL PVC JOINTS ARE TO BE PRIMED, PRIMER IS TO BE PURPLE IN COLOR PER UPC 5) COND. PIPE TO BE BLOCKED UP OFF ROOF MINIMUM 1.5" 6) PVC PIPE EXPOSED TO DAYLIGHT IS TO BE UV COATED 7) REMOVE THREADS FROM DISCHARGE END OF COND. PIPE 8) ELECTRIC CONDUIT TO BE BLOCKED UP OFF ROOF MINIMUM 1.5" 9) ITEMS DATED 12/13/10 HAVE BEEM CORRECTED |
|
| 12/13/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE LADDER FOR ROOF ACCESS 2) PROVIDE SEDIMENT TRAP AT W/H GAS PIPING 3) W/H FLUE PIPING NOT INSTALLED PROPERLY (FITTING NOT TIGHT, SHOWING CRIMP) |