Permit: T10CM02915
Permit Details
Apply Date:
10/20/2010
Applicant:
N/A
Description:
TI:PARISH HALL
Contractors:
- PIONEER PLUMBING INC ,
Permit Reviews
Permit Number - T10CM02915
Permit Status: Expired
Permit Description: TI:PARISH HALL
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
01/11/2011 | REVISION - - 1ST | 01/11/2011 | COMPLETED |
05/31/2011 | REVISION - - 2ND | 06/01/2011 | COMPLETED |
06/01/2011 | REVISION - - 2ND | 06/10/2011 | COMPLETED |
10/20/2010 | COMMERCIAL TI | 10/22/2010 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T10CM02915
Permit Status: Expired
Permit Description: TI:PARISH HALL
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
10/20/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T10CM02915
Permite Description: TI:PARISH HALL
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
BUILDING - FINAL | N/A | Not Inspected | ||
11/29/2011 | MECHANICAL - FINAL | N/A | Partial Approval | IVRS - Inspection :* 1) EXTEND VENTS IN CONDENSATE DRAINS ABOVE FAN COIL DRAIN PANS 2) MARK FAN COIL DATA PLATES WITH HEAT STRIP AND FUSE ACCORDINGLY 3) MARK HEAT PUMP DATA PLATE 4) PROVIDE PROPER SUPPORT FOR MINI SPLIT CONDENSOR 5) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX TO MINIM SPLIT CONDENSOR 6) BLOCK AND CLAMP CONDENSATE DRAIN TO ROOF TOP UNIT 7) PROVIDE A FRESH AIR INTAKE ON ROOF TOP UNIT 8) PROVIDE A FRESH AIR INTAKE BALANCE REPORT 9) NEED TO TEST DUCT SMOKE DETECTORS AND PROVIDE AUDIBLE AND VISIBLE ALARMS |
Completed Inspections
Permit Status: Expired
Permit Number: T10CM02915
Permit Description: TI:PARISH HALL
Total Completed Inspections - 9
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/14/2011 | PLUMBING - PRE SLAB | RRICH | Approved | IVRS - Inspection :* |
02/14/2011 | PLUMBING - ROUGH, SOIL | RRICH | Approved | IVRS - Inspection :* |
02/15/2011 | PLUMBING - INTERMEDIATE | RRICH | Approved | IVRS - Inspection :* |
03/07/2011 | PLUMBING - FINAL | RRICH | Approved | IVRS - Inspection :* |
03/07/2011 | PLUMBING - PROGRESS | RRICH | Approved | IVRS - Inspection :$ |
08/05/2011 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* 1) GET DIRECTION FROM ENGINEER ABOVE SECONDARY OVERFLOW SENSOR FOR FAN COILS 2) NEED TO SEE MINI SPLIT DRAIN CONNECTIONS |
11/22/2011 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection :* |
11/22/2011 | ELECTRIC - INTERMEDIATE | DSANTACR | Approved | IVRS - Inspection :* |
11/29/2011 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* |