Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) EXTEND VENTS IN CONDENSATE DRAINS ABOVE FAN COIL DRAIN PANS 2) MARK FAN COIL DATA PLATES WITH HEAT STRIP AND FUSE ACCORDINGLY 3) MARK HEAT PUMP DATA PLATE 4) PROVIDE PROPER SUPPORT FOR MINI SPLIT CONDENSOR 5) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX TO MINIM SPLIT CONDENSOR 6) BLOCK AND CLAMP CONDENSATE DRAIN TO ROOF TOP UNIT 7) PROVIDE A FRESH AIR INTAKE ON ROOF TOP UNIT 8) PROVIDE A FRESH AIR INTAKE BALANCE REPORT 9) NEED TO TEST DUCT SMOKE DETECTORS AND PROVIDE AUDIBLE AND VISIBLE ALARMS |