Description:
REPLACE; 5 TON GROUND MOUNT SPLIT SYSTEM & WATER HEATER (APA)
Contractors:
  • AMERICAN HOME MAINTENANCE INC *APA*

Outstanding Activity Conditions

Permit Number - T10CM02837
Permit Status: Expired
Permit Description: REPLACE; 5 TON GROUND MOUNT SPLIT SYSTEM & WATER HEATER (APA)
Total Outstanding Activity Conditions - 1
Date Name
10/12/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10CM02837
Permite Description: REPLACE; 5 TON GROUND MOUNT SPLIT SYSTEM & WATER HEATER (APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
04/01/2011 PLUMBING - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE SUPPORT ON CONDENSATE DRAIN INTO PUMP OR CUT BOTTOM OF PIPE AT 45 DEGREE ANGLE
2) PROVIDE HOSE CLAMPS AT CONNECTIONS TO PUMP AND COPPER LINE
3) TIGHTEN ROMEX CONNECTOR ONTO POWER CORD AT FURNACE
4) T & P DRAIN CANNOT RUN UP TO ROOF-USE ALTERNATE METHOD IF NECESSARY. PROVIDE A SMITTY PAN
5) PROVIDE THE REQUIRED GFI SERVICE RECEPT AT THE CONDENSOR
6) REFER LINE INSULATION ON ROOF IS ROTTED. REPLACE DAMAGED INSULATION AND PROVIDE PROTECTIVE COATING
7) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT

Completed Inspections

Permit Status: Expired
Permit Number: T10CM02837
Permit Description: REPLACE; 5 TON GROUND MOUNT SPLIT SYSTEM & WATER HEATER (APA)
Total Completed Inspections - 1
Date Description Inspector Results Comments
04/18/2011 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*