Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/01/2011 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SUPPORT ON CONDENSATE DRAIN INTO PUMP OR CUT BOTTOM OF PIPE AT 45 DEGREE ANGLE 2) PROVIDE HOSE CLAMPS AT CONNECTIONS TO PUMP AND COPPER LINE 3) TIGHTEN ROMEX CONNECTOR ONTO POWER CORD AT FURNACE 4) T & P DRAIN CANNOT RUN UP TO ROOF-USE ALTERNATE METHOD IF NECESSARY. PROVIDE A SMITTY PAN 5) PROVIDE THE REQUIRED GFI SERVICE RECEPT AT THE CONDENSOR 6) REFER LINE INSULATION ON ROOF IS ROTTED. REPLACE DAMAGED INSULATION AND PROVIDE PROTECTIVE COATING 7) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT |