Permit Details

Status:
Final
Type:
SINGLE FAMILY ADDITION
Address NEW:
2157 W TANGLEWOOD DR
Apply Date:
09/28/2010
Applicant:
N/A
Description:
INSTALL:GRID TIED ROOF MOUNTED PHOTOVOLTAIC
Contractors:
  • ARIZONA PRO SOLAR LLC

Permit Reviews

Permit Number - T10CM02698
Permit Status: Final
Permit Description: INSTALL:GRID TIED ROOF MOUNTED PHOTOVOLTAIC
Start Date Submittal Complete Date Status  
09/28/2010 RESIDENTIAL BLDG/ZONING-WALKTHRU 09/28/2010 COMPLETED Review Details
09/28/2010 RESIDENTIAL BLDG/WWM 01/18/2011 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T10CM02698
Permit Status: Final
Permit Description: INSTALL:GRID TIED ROOF MOUNTED PHOTOVOLTAIC
Total Outstanding Activity Conditions - 1
Date Name
09/28/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T10CM02698
Permit Description: INSTALL:GRID TIED ROOF MOUNTED PHOTOVOLTAIC
Total Completed Inspections - 4
Date Description Inspector Results Comments
11/17/2010 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection :*
1) CALLED INTO TEP-SERVICE INCR ONLY-PV NOT READY
2) NEW 3/4" PVC AND WIRING NOT ON PLAN-OBTAIN PERMIT FOR THIS OR MODIFY THIS PERMIT AND PLAN TO SHOW WORK DONE
3) CONDUIT MUST BE 18" MINIMUM DEPTH
4) ROMEX NOT APPROVED FOR U.G. OR WET LOCATION
NOTE: SOLAR NOT INSTALLED YET
11/18/2010 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED PER D. SANTACRUZ
01/25/2011 BUILDING - FINAL RHOLLAND Approved IVRS - Inspection :*
01/26/2011 PERMIT FINALED JWEATHER Approved

Documents

File Name Document Type  
None CONSTRPLANS VIEW
None DOCUMENTS VIEW