Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) A TRIP HAZARD EXIST IN FRONT OF EQUIPMENT 110.26- CUSTOMER WILL TAKE CARE OF 2) PVC CONDUIT AND RECEPT HAVE BEEN REMOVED-A PERMIT WILL BE NEEDED IF RE-INSTALLED |
|
| 01/21/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/12/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio |
|
| 01/05/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/04/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 11/17/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CALLED INTO TEP-SERVICE INCR ONLY-PV NOT READY 2) NEW 3/4" PVC AND WIRING NOT ON PLAN-OBTAIN PERMIT FOR THIS OR MODIFY THIS PERMIT AND PLAN TO SHOW WORK DONE 3) CONDUIT MUST BE 18" MINIMUM DEPTH 4) ROMEX NOT APPROVED FOR U.G. OR WET LOCATION NOTE: SOLAR NOT INSTALLED YET |