Inspection Status: Partial Approval
Inspection History: ELECTRIC - PROGRESS
Permit Number - T10CM02692
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Partial Approval
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/10/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) NO MORE THAN 300V TO GROUND BETWEEN DEVICES 404.8 (B) 2) TIGHTEN LOOSE FITTINGS 3) SECURE MC CABLE 6' INTERVALS 4) PROTECT END OF RACEWAY VDV CABLING FRO SHARP METAL EDGES 5) IDENTIFY FIRE ALARM BOXES 6) OK WALLS 105-111. BREAK ROOM UPSTAIRS AND AFTER CORRECTION |