Permit: T10CM02692
Permit Details
Status:
Expired
Type:
COMMERCIAL ADDITION
Address:
6601 S RENAISSANCE DR
Address NEW:
6601 S RENAISSANCE DR
Apply Date:
09/27/2010
Applicant:
N/A
Description:
ADD MANUFACTORING SPACE TO EXISTING FACTORY "TUCSON PRECISION PRODUCTS"
Architects:
- WILSON, LAWRENCE R
Contractors:
- WILSON AND ASSOCIATES DESIGN GRO
Permit Reviews
Permit Number - T10CM02692
Permit Status: Expired
Permit Description: ADD MANUFACTORING SPACE TO EXISTING FACTORY "TUCSON PRECISION PRODUCTS"
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/10/2011 | REVISION - - 1ST | 01/25/2011 | COMPLETED |
| 04/19/2011 | REVISION - - 2ND | 04/19/2011 | COMPLETED |
| 04/19/2011 | REVISION - - 2ND | 05/10/2011 | COMPLETED |
| 04/27/2011 | REVISION - - 3RD | 04/27/2011 | COMPLETED |
| 05/10/2011 | REVISION - - 2ND | 05/10/2011 | COMPLETED |
| 09/27/2010 | PLANS OK TO SUBMIT - COMM | 09/27/2010 | COMPLETED |
| 09/28/2010 | COMMERCIAL NEW | 10/28/2010 | COMPLETED |
| 11/17/2010 | RESUBMITTAL | 12/08/2010 | COMPLETED |
| 12/08/2010 | RESUBMITTAL | 12/30/2010 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T10CM02692
Permit Status: Expired
Permit Description: ADD MANUFACTORING SPACE TO EXISTING FACTORY "TUCSON PRECISION PRODUCTS"
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/27/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T10CM02692
Permite Description: ADD MANUFACTORING SPACE TO EXISTING FACTORY "TUCSON PRECISION PRODUCTS"
Total Outstanding Inspections - 5
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| PLUMBING - GAS PRESS TEST FNL | N/A | Not Inspected | ||
| FIRE SPKLR - FINAL | N/A | Not Inspected | ||
| 06/10/2011 | ELECTRIC - PROGRESS | N/A | Partial Approval | IVRS - Inspection :* 1) NO MORE THAN 300V TO GROUND BETWEEN DEVICES 404.8 (B) 2) TIGHTEN LOOSE FITTINGS 3) SECURE MC CABLE 6' INTERVALS 4) PROTECT END OF RACEWAY VDV CABLING FRO SHARP METAL EDGES 5) IDENTIFY FIRE ALARM BOXES 6) OK WALLS 105-111. BREAK ROOM UPSTAIRS AND AFTER CORRECTION |
| 06/16/2011 | ELECTRIC - CABLE DROP | N/A | Partial Approval | IVRS - Inspection :* 1) RECEIVED GFI TEST 2) CONTRACTOR TO MAINTAIN LOCKOUT/TAG OUT 3) NEED LETTER OR TORQUE |
| 07/15/2011 | FIRE - LANE SIGNS | N/A | Denied | Fire apparatus access roads 20 to 28 feet shall have a Fire Access Road sign on both sides of road in the direction of travel. Roads greater then 28 up to 36 feet require a sign on one side in the direction of travel. The signs need to face both directions since the access road is not a one way street. |
Completed Inspections
Permit Status: Expired
Permit Number: T10CM02692
Permit Description: ADD MANUFACTORING SPACE TO EXISTING FACTORY "TUCSON PRECISION PRODUCTS"
Total Completed Inspections - 43
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2011 | PLUMBING - ROUGH, SOIL | BBENEDON | Approved | IVRS - Inspection :* |
| 02/24/2011 | PLUMBING - BACK WATER VALVE | RRICH | Approved | IVRS - Inspection :* 1) 4" SEWER FROM BLDG TO TIE IN |
| 02/24/2011 | PLUMBING - YARD WTR LINE/TEST | RRICH | Approved | IVRS - Inspection :* |
| 02/24/2011 | PLUMBING - PRE SLAB | RRICH | Approved | IVRS - Inspection :* |
| 05/02/2011 | ELECTRIC - UFER | DSANTACR | Approved | IVRS - Inspection :* |
| 05/18/2011 | EXCAVATION/LAYOUT REBAR & ZON | MHENSON | Approved | IVRS - Inspection :* |
| 05/25/2011 | BUILDING PRE-SLAB | MHENSON | Approved | IVRS - Inspection :* |
| 06/03/2011 | PLUMBING - GAS PRESSURE TEST | RRICH | Approved | IVRS - Inspection :* 1) FROM METER THRU TO ALL UH UNIT SHUT OFF VALVES. 60 PSI TEST OK 2) RETEST TO 10 PSI FOR WATER HEATER VALVE INSTALL |
| 06/20/2011 | TEP CLEARANCE - AM | JWEATHER | Approved | TEC CLEARED PER R. HOLLANDER |
| 06/21/2011 | SHEET ROCK NAILING | MHENSON | Approved | IVRS - Inspection :* |
| 06/23/2011 | PLUMBING - ROOF DRAINS | RRICH | Approved | IVRS - Inspection :* PROVIDE HANGERS AT NORTH WEST CORNER AS REQUIRED |
| 06/24/2011 | FIRE SPKLR - UG, PIPING, HYDRO | DSIWARSKI | Approved | |
| 06/24/2011 | FIRE - HYDRANTS | DSIWARSKI | Approved | |
| 07/01/2011 | RIGHT OF WAY - FINAL | MCASTRO | Approved | |
| 07/06/2011 | MECHANICAL - ABOVE CEILING | MRAMBER | Approved | IVRS - Inspection :* |
| 07/06/2011 | U VALUE FOR WINDOW | MHENSON | Approved | IVRS - Inspection :* |
| 07/06/2011 | PLUMBING - ABOVE CEILING | RRICH | Approved | IVRS - Inspection :* |
| 07/06/2011 | NPPO - FINAL | RDLD | Approved | |
| 07/07/2011 | ELECTRIC - ABOVE CEILING | DSANTACR | Approved | IVRS - Inspection :* |
| 07/08/2011 | LANDSCAPE - FINAL | RDLD | Approved | |
| 07/15/2011 | MECHANICAL - HOODS | MRAMBER | Approved | IVRS - Inspection :* |
| 07/15/2011 | PLUMBING - INTERMEDIATE | RRICH | Approved | IVRS - Inspection :* |
| 07/15/2011 | OUTDOOR LIGHTING FINAL | DSANTACR | Approved | IVRS - Inspection :* |
| 07/15/2011 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection :* |
| 07/15/2011 | ELECTRIC - OUTDOOR LIGHTING | DSANTACR | Approved | IVRS - Inspection :* |
| 07/15/2011 | ELECTRIC - TEMPORARY SERVICE | DSANTACR | Approved | IVRS - Inspection :* |
| 07/15/2011 | ELECTRIC - INTERMEDIATE | DSANTACR | Approved | IVRS - Inspection :* |
| 07/15/2011 | ELECTRIC - UNDERGROUND | DSANTACR | Approved | IVRS - Inspection :* |
| 07/18/2011 | SIGN - FINAL | RDLD | Approved | |
| 07/19/2011 | MECHANICAL - INTERMEDIATE | MRAMBER | Approved | IVRS - Inspection :* |
| 07/19/2011 | BUILDING ABOVE CEILING | MHENSON | Approved | IVRS - Inspection :* |
| 07/19/2011 | FRAMING | MHENSON | Approved | IVRS - Inspection :* |
| 07/19/2011 | PLUMBING - FINAL | RRICH | Approved | IVRS - Inspection :* |
| 07/19/2011 | PLUMBING - PROGRESS | RRICH | Approved | IVRS - Inspection :* |
| 07/20/2011 | CERTIFICATE OF OCCUPANCY | MHENSON | Approved | IVRS - Inspection :* 1) WILL APPROVE WITH BLDG FINAL |
| 07/20/2011 | BUILDING - FINAL | MHENSON | Approved | IVRS - Inspection :* 1) WILL APPROVE WITH CALLS FOR MECH, FIRE AND ENGINEERING 2) DABBS LIST DONE |
| 07/20/2011 | MECHANICAL - FINAL | MRAMBER | Approved | IVRS - Inspection :* |
| 07/20/2011 | STEM WALL/RETAINING WALL | MHENSON | Approved | IVRS - Inspection :* |
| 07/20/2011 | BUILDING - PROGRESS | MHENSON | Approved | IVRS - Inspection :* |
| 07/20/2011 | ROOF NAILING | MHENSON | Approved | IVRS - Inspection :* |
| 07/20/2011 | EXT METAL CLIPS/EXT SHEATHING | MHENSON | Approved | IVRS - Inspection :* |
| 07/21/2011 | ENGINEERING - FINAL | RDLD | Approved | |
| 07/21/2011 | ENGINEERING - FINAL | RDLD | Approved |