Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
4808 E HAMPTON ST
Apply Date:
09/07/2010
Applicant:
N/A
Description:
NEW ROOFTOP A/C UNIT

Permit Reviews

Permit Number - T10CM02473
Permit Status: Expired
Permit Description: NEW ROOFTOP A/C UNIT
Start Date Submittal Complete Date Status  
09/07/2010 OTHER 09/07/2010 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T10CM02473
Permit Status: Expired
Permit Description: NEW ROOFTOP A/C UNIT
Total Outstanding Activity Conditions - 1
Date Name
09/07/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10CM02473
Permite Description: NEW ROOFTOP A/C UNIT
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
09/09/2010 BUILDING - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A TRAP ON CONDENSATE DRAIN SUPPORT EVERY 4'. USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
2) PROVIDE A BUSHING IN ELECTRIC DISCONNECT. DO NOT USE WHITE WIRE TO POWER THE A/C UNIT. FINISH CLAMPING ELECTRIC CONDUIT
3) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF
4) ALL DUCT IN ATTIC MUST BE INSULATED WITH MINIMUM R8 INSULATION AND FLEX DUCTS SUPPORTED EVERY 5'
5) ROOF DRAWING INCOMPLETE. CLARIFICATION REQUIRED FOR STRUCTURAL SUPPORT OF A/C UNIT. ROOF IS PITCHED AND BEARING WALL DOES NOT APPLY
6) ID CIRCUIT BREAKER
09/09/2010 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/09/2010 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*