Permit: T10CM02473

Parcel: 121101060


Addresses:

4808 E HAMPTON ST

Inspection Status: Denied

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
09/09/2010 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A TRAP ON CONDENSATE DRAIN SUPPORT EVERY 4'. USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
2) PROVIDE A BUSHING IN ELECTRIC DISCONNECT. DO NOT USE WHITE WIRE TO POWER THE A/C UNIT. FINISH CLAMPING ELECTRIC CONDUIT
3) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF
4) ALL DUCT IN ATTIC MUST BE INSULATED WITH MINIMUM R8 INSULATION AND FLEX DUCTS SUPPORTED EVERY 5'
5) ROOF DRAWING INCOMPLETE. CLARIFICATION REQUIRED FOR STRUCTURAL SUPPORT OF A/C UNIT. ROOF IS PITCHED AND BEARING WALL DOES NOT APPLY
6) ID CIRCUIT BREAKER