Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Apply Date:
06/01/2010
Applicant:
N/A
Description:
UPGRADE ELECTRIC TO 200 AMPS, REPLACE AC UNITS
Contractors:
  • J W SHAFFER ELECTRIC CO. **C**

Permit Reviews

Permit Number - T10CM01491
Permit Status: Expired
Permit Description: UPGRADE ELECTRIC TO 200 AMPS, REPLACE AC UNITS
Start Date Submittal Complete Date Status  
06/01/2010 OTHER 06/01/2010 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T10CM01491
Permit Status: Expired
Permit Description: UPGRADE ELECTRIC TO 200 AMPS, REPLACE AC UNITS
Total Outstanding Activity Conditions - 1
Date Name
06/01/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10CM01491
Permite Description: UPGRADE ELECTRIC TO 200 AMPS, REPLACE AC UNITS
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
07/22/2010 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDENSATE TRAP NOT BUILT CORRECTLY.
SEE MANUFACTURES INSTALL INSTRUCTIONS FOR PROPER DEPTH. VENT MUST BE DOWNSTREAM OF TRAP. PAINT WITH LATEX PAINT, PROVIDE PURPLE PRIMER PRIOR TO GLUE, TERMINATE WITHIN 6" OF THE DIRT
2) PROVIDE A FRESH AIR INTAKE
3) PROVIDE THE REQUIRED GFI SERVICE RECEPT
4) PROVIDE MINIMUM 2" R8 DUCT LINER IN ALL NEW ROOF TOP DUCTING
5) IS THERE A HEAT STRIP ? MARK DATA PLATE AND FUSE ACCORDINGLY
6) SLEEPERS UNDER A/C UNIT HAVE BEEN CUT IN HALF. MUST BE FULL LENGTH, USE AN ANGLE IRON STAND OR RELOCATE ELECTRIC CONDUIT

Completed Inspections

Permit Status: Expired
Permit Number: T10CM01491
Permit Description: UPGRADE ELECTRIC TO 200 AMPS, REPLACE AC UNITS
Total Completed Inspections - 3
Date Description Inspector Results Comments
06/16/2010 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED PER R. MORENO ON 06/15/10 AT 9:15 AM
07/22/2010 ELECTRIC - SERVICE UPGRADE RMORENO Approved
07/22/2010 ELECTRIC - FINAL RMORENO Approved IVRS - Inspection :*