Permit: T10CM01491
Permit Details
Apply Date:
06/01/2010
Applicant:
N/A
Description:
UPGRADE ELECTRIC TO 200 AMPS, REPLACE AC UNITS
Contractors:
- J W SHAFFER ELECTRIC CO. **C**
Permit Reviews
Permit Number - T10CM01491
Permit Status: Expired
Permit Description: UPGRADE ELECTRIC TO 200 AMPS, REPLACE AC UNITS
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
06/01/2010 | OTHER | 06/01/2010 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T10CM01491
Permit Status: Expired
Permit Description: UPGRADE ELECTRIC TO 200 AMPS, REPLACE AC UNITS
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
06/01/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T10CM01491
Permite Description: UPGRADE ELECTRIC TO 200 AMPS, REPLACE AC UNITS
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/22/2010 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE TRAP NOT BUILT CORRECTLY. SEE MANUFACTURES INSTALL INSTRUCTIONS FOR PROPER DEPTH. VENT MUST BE DOWNSTREAM OF TRAP. PAINT WITH LATEX PAINT, PROVIDE PURPLE PRIMER PRIOR TO GLUE, TERMINATE WITHIN 6" OF THE DIRT 2) PROVIDE A FRESH AIR INTAKE 3) PROVIDE THE REQUIRED GFI SERVICE RECEPT 4) PROVIDE MINIMUM 2" R8 DUCT LINER IN ALL NEW ROOF TOP DUCTING 5) IS THERE A HEAT STRIP ? MARK DATA PLATE AND FUSE ACCORDINGLY 6) SLEEPERS UNDER A/C UNIT HAVE BEEN CUT IN HALF. MUST BE FULL LENGTH, USE AN ANGLE IRON STAND OR RELOCATE ELECTRIC CONDUIT |
Completed Inspections
Permit Status: Expired
Permit Number: T10CM01491
Permit Description: UPGRADE ELECTRIC TO 200 AMPS, REPLACE AC UNITS
Total Completed Inspections - 3
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/16/2010 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER R. MORENO ON 06/15/10 AT 9:15 AM |
07/22/2010 | ELECTRIC - SERVICE UPGRADE | RMORENO | Approved | |
07/22/2010 | ELECTRIC - FINAL | RMORENO | Approved | IVRS - Inspection :* |