Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE TRAP NOT BUILT CORRECTLY. SEE MANUFACTURES INSTALL INSTRUCTIONS FOR PROPER DEPTH. VENT MUST BE DOWNSTREAM OF TRAP. PAINT WITH LATEX PAINT, PROVIDE PURPLE PRIMER PRIOR TO GLUE, TERMINATE WITHIN 6" OF THE DIRT 2) PROVIDE A FRESH AIR INTAKE 3) PROVIDE THE REQUIRED GFI SERVICE RECEPT 4) PROVIDE MINIMUM 2" R8 DUCT LINER IN ALL NEW ROOF TOP DUCTING 5) IS THERE A HEAT STRIP ? MARK DATA PLATE AND FUSE ACCORDINGLY 6) SLEEPERS UNDER A/C UNIT HAVE BEEN CUT IN HALF. MUST BE FULL LENGTH, USE AN ANGLE IRON STAND OR RELOCATE ELECTRIC CONDUIT |
|
| 07/14/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |