Permit Details

Status:
Expired
Type:
SINGLE FAMILY COMPLIANCE
Address NEW:
7661 E PERSIMMON DR
Apply Date:
03/18/2010
Applicant:
N/A
Description:
CODE COMPLIANCE FOR BEDRM ADDTS AND LAUNDRY

Permit Reviews

Permit Number - T10CM00672
Permit Status: Expired
Permit Description: CODE COMPLIANCE FOR BEDRM ADDTS AND LAUNDRY
Start Date Submittal Complete Date Status  
03/18/2010 RESIDENTIAL BLDG/ZONING-WALKTHRU 03/23/2010 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T10CM00672
Permit Status: Expired
Permit Description: CODE COMPLIANCE FOR BEDRM ADDTS AND LAUNDRY
Total Outstanding Activity Conditions - 1
Date Name
03/18/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10CM00672
Permite Description: CODE COMPLIANCE FOR BEDRM ADDTS AND LAUNDRY
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
BUILDING - PROGRESS N/A Not Inspected
03/25/2010 BUILDING - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO PAPERWORK LEFT ON SITE
2) YOU DON'T NEED A CODE COMPLIANCE, YOU NEED PERMITS TO REPAIR OR REMOVE STRUCTURES
3) SERVICE ELECTRIC AT METER RAISE 1/0 AL. FEEDERS FROM METER HAVE BEEN CUT AND SPLICED TO CU. 2/0
4) OLD SERVICE PANEL TURNED INTO J-BOX, IMPROPER CLEARANCE FOR SERVICE WIRES
5) SUB PANEL NOT WIRED CORRECTLY TO MANY VIOLATIONS, WIRE SIZES, BREAKER DON'T MATCH PANEL, NEUTRALS GROUNDS NOT ISOLATE, WIRE AND SIZE OF BREAKER, LABELING, COLOR CODES FOR WIRES
6) MISSING FIXTURES THRU OUT
7) CEILINGS/WALLS, BOTTOM PLATES AND WIRING OF ADDED ON CONSTRUCTION TO BE OPENED UP FOR INSPECTION
8) TWO ROOMS WITHOUT HEAT SOURCE, WINDOW A/C UNIT TO BE ON IT'S OWN CIRCUIT
9) WASHER DRAIN, DRAINS INTO KIT SINK CLEANOUT
10) IF SHED IS LEGAL, REMOVE ALL WIRING OR BRING UP TO CODE
11) REAR ADDITION 2 X 4 RAFTERS ALSO PORCH, BEAM TO SMALL 2 X 4 RAFTERS TO SMALL
12) FURNACE ROOM NUMEROUS VIOLATIONS, WITH GAS, FURNACE H20 HTR FLUES, COMBUSTION AIR, FLEX LINES, SW GAS SHUT OFF TAG FOR UNSAFE SITUATION
13) FLOOR ELEV.
14) REMOVAL OF HTR
15) ROOF MECH ELECTRIC
16) STUCCO ALL HOUSE, MATERIALS ?
17) EXT. GRADE HT. TO WOOD, PLATE F.F. H20 SEPERATE
18) PROPERTY PINS
19) NO HOT H20 IN LAUNDRY