Inspection History Details
Inspection Status: Denied
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/25/2010 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO PAPERWORK LEFT ON SITE 2) YOU DON'T NEED A CODE COMPLIANCE, YOU NEED PERMITS TO REPAIR OR REMOVE STRUCTURES 3) SERVICE ELECTRIC AT METER RAISE 1/0 AL. FEEDERS FROM METER HAVE BEEN CUT AND SPLICED TO CU. 2/0 4) OLD SERVICE PANEL TURNED INTO J-BOX, IMPROPER CLEARANCE FOR SERVICE WIRES 5) SUB PANEL NOT WIRED CORRECTLY TO MANY VIOLATIONS, WIRE SIZES, BREAKER DON'T MATCH PANEL, NEUTRALS GROUNDS NOT ISOLATE, WIRE AND SIZE OF BREAKER, LABELING, COLOR CODES FOR WIRES 6) MISSING FIXTURES THRU OUT 7) CEILINGS/WALLS, BOTTOM PLATES AND WIRING OF ADDED ON CONSTRUCTION TO BE OPENED UP FOR INSPECTION 8) TWO ROOMS WITHOUT HEAT SOURCE, WINDOW A/C UNIT TO BE ON IT'S OWN CIRCUIT 9) WASHER DRAIN, DRAINS INTO KIT SINK CLEANOUT 10) IF SHED IS LEGAL, REMOVE ALL WIRING OR BRING UP TO CODE 11) REAR ADDITION 2 X 4 RAFTERS ALSO PORCH, BEAM TO SMALL 2 X 4 RAFTERS TO SMALL 12) FURNACE ROOM NUMEROUS VIOLATIONS, WITH GAS, FURNACE H20 HTR FLUES, COMBUSTION AIR, FLEX LINES, SW GAS SHUT OFF TAG FOR UNSAFE SITUATION 13) FLOOR ELEV. 14) REMOVAL OF HTR 15) ROOF MECH ELECTRIC 16) STUCCO ALL HOUSE, MATERIALS ? 17) EXT. GRADE HT. TO WOOD, PLATE F.F. H20 SEPERATE 18) PROPERTY PINS 19) NO HOT H20 IN LAUNDRY |