Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
1501 W SAINT MARYS RD
Apply Date:
12/22/2010
Applicant:
ANOZIRA FIRE PROTECTION L L C
Description:
FIRE HOOD SUPPRESSION SYSTEM
Contractors:
  • ANOZIRA FIRE PROTECTION L L C

Permit Reviews

Permit Number - T10BU01901
Permit Status: Expired
Permit Description: FIRE HOOD SUPPRESSION SYSTEM
Start Date Submittal Complete Date Status  
12/22/2010 MECHANICAL 12/22/2010 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T10BU01901
Permit Status: Expired
Permit Description: FIRE HOOD SUPPRESSION SYSTEM
Total Outstanding Activity Conditions - 1
Date Name
12/22/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10BU01901
Permite Description: FIRE HOOD SUPPRESSION SYSTEM
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
FIRE - KITCHEN EXH HOOD FINAL N/A Not Inspected
12/23/2010 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DUCT IS TO BE WELDED TO HOOD
2) EXHAUST FAN NOT ON APPROVED CURB
3) PROVIDE HINGE KIT
4) PROVIDE GREASE RECEPTOR
5) KITCHEN EXHAUST IS TO BE 10' AWAY OR 2' ABOVE COOLER INLET
6) PROVIDE INTERLOCK BETWEEN EXHAUST AND W.W. A.

Documents

File Name Document Type  
001_HOOD.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW