Permit: T10BU01901
Permit Details
Status:
Expired
Type:
COMMERCIAL OTHER
Address:
1501 W SAINT MARYS RD
Address NEW:
1501 W SAINT MARYS RD
Apply Date:
12/22/2010
Applicant:
ANOZIRA FIRE PROTECTION L L C
Description:
FIRE HOOD SUPPRESSION SYSTEM
Contractors:
- ANOZIRA FIRE PROTECTION L L C
Permit Reviews
Permit Number - T10BU01901
Permit Status: Expired
Permit Description: FIRE HOOD SUPPRESSION SYSTEM
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 12/22/2010 | MECHANICAL | 12/22/2010 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T10BU01901
Permit Status: Expired
Permit Description: FIRE HOOD SUPPRESSION SYSTEM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/22/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T10BU01901
Permite Description: FIRE HOOD SUPPRESSION SYSTEM
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| FIRE - KITCHEN EXH HOOD FINAL | N/A | Not Inspected | ||
| 12/23/2010 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DUCT IS TO BE WELDED TO HOOD 2) EXHAUST FAN NOT ON APPROVED CURB 3) PROVIDE HINGE KIT 4) PROVIDE GREASE RECEPTOR 5) KITCHEN EXHAUST IS TO BE 10' AWAY OR 2' ABOVE COOLER INLET 6) PROVIDE INTERLOCK BETWEEN EXHAUST AND W.W. A. |