Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DUCT IS TO BE WELDED TO HOOD 2) EXHAUST FAN NOT ON APPROVED CURB 3) PROVIDE HINGE KIT 4) PROVIDE GREASE RECEPTOR 5) KITCHEN EXHAUST IS TO BE 10' AWAY OR 2' ABOVE COOLER INLET 6) PROVIDE INTERLOCK BETWEEN EXHAUST AND W.W. A. |