Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address:
3608 N ORACLE RD
Apply Date:
11/02/2010
Applicant:
SUN DEVIL FIRE EQUIPMENT INC , *C
Description:
INSTALL:HOOD FIRE SUPPESSION SYSTEM
Contractors:
  • SUN DEVIL FIRE EQUIPMENT INC , *C

Permit Reviews

Permit Number - T10BU01659
Permit Status: Final
Permit Description: INSTALL:HOOD FIRE SUPPESSION SYSTEM
Start Date Submittal Complete Date Status  
11/02/2010 MECHANICAL 11/02/2010 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T10BU01659
Permit Status: Final
Permit Description: INSTALL:HOOD FIRE SUPPESSION SYSTEM
Total Outstanding Activity Conditions - 1
Date Name
11/02/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T10BU01659
Permit Description: INSTALL:HOOD FIRE SUPPESSION SYSTEM
Total Completed Inspections - 2
Date Description Inspector Results Comments
12/07/2010 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :
See detailed listing on site.| 999*
MEET MARISA AT 9:00 AM TUES:
1) GREASE DUCT NOT ATTACHED TO HOOD BY APPROVED MEANS
2) HOOD NOT OF TYPE I CONSTRUCTION
3) GREASE DUCT NOT WITHIN CHASE OR FIRE WRAP
4) GREASE DUCT DOES NOT EXTEND UP TO CURB, GREASE IS BLDG UP AROUND DUCT INSIDE OF CURB
5) FAN NOT PROPERLY WIRED
6) FAN HAS NO HINGE KIT
7) FAN NOT PROPERLY MOUNTED TO CURB
8) CURB NOT OF VENTED CONSTRUCTION
9) FAN HAS NO GREASE RECEPTOR
10) HOOD HAS LARGE HOLES IN REAR OF HOOD AND WHERE DUCT PENTRATES
11) HOOD HAS NO MAKE UP AIR
04/28/2011 FIRE - KITCHEN EXH HOOD FINAL WMOTTO Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW
001_HOOD.TIF.TIF FIRE PLANS VIEW