Permit: T10BU01659

Parcel: 10602262A


Addresses:

3608 N ORACLE RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10BU01659

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/28/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/27/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
12/07/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
MEET MARISA AT 9:00 AM TUES:
1) GREASE DUCT NOT ATTACHED TO HOOD BY APPROVED MEANS
2) HOOD NOT OF TYPE I CONSTRUCTION
3) GREASE DUCT NOT WITHIN CHASE OR FIRE WRAP
4) GREASE DUCT DOES NOT EXTEND UP TO CURB, GREASE IS BLDG UP AROUND DUCT INSIDE OF CURB
5) FAN NOT PROPERLY WIRED
6) FAN HAS NO HINGE KIT
7) FAN NOT PROPERLY MOUNTED TO CURB
8) CURB NOT OF VENTED CONSTRUCTION
9) FAN HAS NO GREASE RECEPTOR
10) HOOD HAS LARGE HOLES IN REAR OF HOOD AND WHERE DUCT PENTRATES
11) HOOD HAS NO MAKE UP AIR