Permit: T10BU01314
Permit Details
Status:
Expired
Type:
COMMERCIAL OTHER
Address:
1212 S PALO VERDE AV
Address NEW:
1212 S PALO VERDE AV
Apply Date:
08/18/2010
Applicant:
O E M FIRE AND SECURITY L L C
Description:
INSTALL:FIRE ALARM
Contractors:
- O E M FIRE AND SECURITY L L C
Outstanding Activity Conditions
Permit Number - T10BU01314
Permit Status: Expired
Permit Description: INSTALL:FIRE ALARM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/18/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T10BU01314
Permite Description: INSTALL:FIRE ALARM
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/23/2011 | FIRE - ALARM FINAL | N/A | Partial Approval | 1. Lockout required on electrical circuit breaker. 2. Plans show 12AH battery but (2) 7AH batteries are installed. Need to submit as-builds or change batteries. |