Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T10BU01314

Parcel: 13007204A

Inspection Status: Partial Approval

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
11/23/2011 FIRE - ALARM FINAL Partial Approval 1. Lockout required on electrical circuit breaker.
2. Plans show 12AH battery but (2) 7AH batteries are installed. Need to submit as-builds or change batteries.