Permit: T10BU01314

Parcel: 13007204A

Inspection Status: Partial Approval

Inspection History: FIRE - ALARM FINAL

Permit Number - T10BU01314

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
11/23/2011 FIRE - ALARM FINAL Partial Approval 1. Lockout required on electrical circuit breaker.
2. Plans show 12AH battery but (2) 7AH batteries are installed. Need to submit as-builds or change batteries.