Permit: T10BU00781
Permit Details
Apply Date:
05/13/2010
Applicant:
NEWMAN PLUMBING L L C
Description:
Install 30' of 2" underground & 35 fire sprinklers
Contractors:
- NEWMAN PLUMBING L L C
Outstanding Activity Conditions
Permit Number - T10BU00781
Permit Status: Expired
Permit Description: Install 30' of 2" underground & 35 fire sprinklers
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/13/2010 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T10BU00781
Permite Description: Install 30' of 2" underground & 35 fire sprinklers
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| PERMIT FINALED | N/A | Not Inspected | ||
| 09/23/2010 | FIRE SPKLR - FINAL | N/A | Denied | 1. ADD ONE HEAD IN CLOSET 2. NEED AS BUILTS FOR CHANGES |
Completed Inspections
Permit Status: Expired
Permit Number: T10BU00781
Permit Description: Install 30' of 2" underground & 35 fire sprinklers
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2010 | FIRE SPKLR - UG PIPING FLUSH | DRamirez | Approved | Approved 9/17/10 |
| 09/17/2010 | FIRE SPKLR - UG, PIPING, HYDRO | DRamirez | Approved | Approved 9/17/10 |
| 09/23/2010 | FIRE SPKLR - OH PIPING & HYDRO | CSCHULTZ | Approved | 200 PSI FOR 2 HOURS |