Inspection Status: Partial Approval
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/16/2012 | FIRE SPKLR - FINAL | Partial Approval | Sprinkler system is partially approve all they will need to do is pull a permit for installation on the fire alarm system and called that permit in when issued. Then the sprinkler final can be given. | |
| 03/13/2012 | FIRE SPKLR - FINAL | Denied | Need to install a indicating type shut off valve on riser with a tamper switch as per your approved plans. Need to set up an approved fire monitoring system for the tamper switch and flow switch. |
|
| 03/12/2012 | FIRE SPKLR - FINAL | Denied | As bults received and approved by M. Brown. Need to call in final | |
| 09/23/2010 | FIRE SPKLR - FINAL | Denied | 1. ADD ONE HEAD IN CLOSET 2. NEED AS BUILTS FOR CHANGES |