Permit: T10BU00781

Parcel: 131091200


Addresses:

5720 E 26TH ST

Inspection Status: Partial Approval

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
04/16/2012 FIRE SPKLR - FINAL Partial Approval Sprinkler system is partially approve all they will need to do is pull a permit for installation on the fire alarm system and called that permit in when issued. Then the sprinkler final can be given.
03/13/2012 FIRE SPKLR - FINAL Denied Need to install a indicating type shut off valve on riser with a tamper switch as per your approved plans.
Need to set up an approved fire monitoring system for the tamper switch and flow switch.
03/12/2012 FIRE SPKLR - FINAL Denied As bults received and approved by M. Brown. Need to call in final
09/23/2010 FIRE SPKLR - FINAL Denied 1. ADD ONE HEAD IN CLOSET
2. NEED AS BUILTS FOR CHANGES