Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
545 N CAMINO SECO
Apply Date:
01/07/2010
Applicant:
SIMPLEX GRINNELL L P
Description:
FIRE ALARM
Contractors:
  • SIMPLEX GRINNELL L P

Outstanding Activity Conditions

Permit Number - T10BU00019
Permit Status: Expired
Permit Description: FIRE ALARM
Total Outstanding Activity Conditions - 1
Date Name
01/07/2010 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T10BU00019
Permite Description: FIRE ALARM
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
01/14/2010 FIRE - ALARM FINAL N/A Denied Not approved 1/14/10
1.) Need to replace the batteries from the main panel from 18 AH to 33 AH as indicated on the approved plans.
2.) Provide documentation indicating the date when the batteries were installed or batteries must be replaced.
3.) Need 2 dedicated phone lines to the Central Monitoring Station as required by the FIRE CODE. Only one is provided.
4.) All appliances ahve been tested and approved..

Documents

File Name Document Type  
001_ALARM.TIF FIRE PLANS VIEW
002_ALARM.TIF FIRE PLANS VIEW
003_ALARM.TIF FIRE PLANS VIEW
004_ALARM.TIF FIRE PLANS VIEW
005_ALARM.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW