Permit: T10BU00019

Parcel: 13329001A


Addresses:

545 N CAMINO SECO


Inspection Status: Denied

Inspection History: FIRE - ALARM FINAL

Permit Number - T10BU00019

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
01/14/2010 FIRE - ALARM FINAL Denied Not approved 1/14/10
1.) Need to replace the batteries from the main panel from 18 AH to 33 AH as indicated on the approved plans.
2.) Provide documentation indicating the date when the batteries were installed or batteries must be replaced.
3.) Need 2 dedicated phone lines to the Central Monitoring Station as required by the FIRE CODE. Only one is provided.
4.) All appliances ahve been tested and approved..