Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - ALARM FINAL
Permit Number - T10BU00019
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/14/2010 | FIRE - ALARM FINAL | Denied | Not approved 1/14/10 1.) Need to replace the batteries from the main panel from 18 AH to 33 AH as indicated on the approved plans. 2.) Provide documentation indicating the date when the batteries were installed or batteries must be replaced. 3.) Need 2 dedicated phone lines to the Central Monitoring Station as required by the FIRE CODE. Only one is provided. 4.) All appliances ahve been tested and approved.. |